/opennms-base-assembly/src/main/filtered/etc/events/Sentry.events.xml

https://github.com/ajakubo1/opennms · XML · 6012 lines · 5512 code · 498 blank · 2 comment · 0 complexity · ce01fe99cbf945d00bf841fb0f4e2867 MD5 · raw file

Large files are truncated click here to view the full file

  1. <!-- Start of auto generated data from MIB: Sentry3-MIB -->
  2. <events xmlns="http://xmlns.opennms.org/xsd/eventconf">
  3. <event>
  4. <mask>
  5. <maskelement>
  6. <mename>id</mename>
  7. <mevalue>.1.3.6.1.4.1.1718.3.100</mevalue>
  8. </maskelement>
  9. <maskelement>
  10. <mename>generic</mename>
  11. <mevalue>6</mevalue>
  12. </maskelement>
  13. <maskelement>
  14. <mename>specific</mename>
  15. <mevalue>1</mevalue>
  16. </maskelement>
  17. <varbind>
  18. <vbnumber>4</vbnumber>
  19. <vbvalue>0</vbvalue>
  20. </varbind>
  21. </mask>
  22. <uei>uei.opennms.org/vendor/ServerTech/traps/towerStatusEvent-Normal</uei>
  23. <event-label>Sentry3-MIB defined trap event: towerStatusEvent-Normal</event-label>
  24. <descr>
  25. &lt;p&gt;Tower status event. If enabled, this trap is sent when the
  26. towerStatus indicates an error state ('noComm', 'fanFail',
  27. or 'overTemp'). This trap is repeated periodically while the
  28. towerStatus remains in an error state. If the towerStatus
  29. returns to a non-error state ('normal'), this trap is sent
  30. once more with the non-error towerStatus, and then stops
  31. being repeated.
  32. While the towerStatus indicates a 'noComm' error state, all
  33. status and load traps are suppressed for input feeds and
  34. outlets on the tower.&lt;/p&gt;&lt;table&gt;
  35. &lt;tr&gt;&lt;td&gt;&lt;b&gt;
  36. systemLocation&lt;/b&gt;&lt;/td&gt;&lt;td&gt;
  37. %parm[#1]%;&lt;/td&gt;&lt;td&gt;&lt;p&gt;&lt;/p&gt;&lt;/td&gt;&lt;/tr&gt;
  38. &lt;tr&gt;&lt;td&gt;&lt;b&gt;
  39. towerID&lt;/b&gt;&lt;/td&gt;&lt;td&gt;
  40. %parm[#2]%;&lt;/td&gt;&lt;td&gt;&lt;p&gt;&lt;/p&gt;&lt;/td&gt;&lt;/tr&gt;
  41. &lt;tr&gt;&lt;td&gt;&lt;b&gt;
  42. towerName&lt;/b&gt;&lt;/td&gt;&lt;td&gt;
  43. %parm[#3]%;&lt;/td&gt;&lt;td&gt;&lt;p&gt;&lt;/p&gt;&lt;/td&gt;&lt;/tr&gt;
  44. &lt;tr&gt;&lt;td&gt;&lt;b&gt;
  45. towerStatus&lt;/b&gt;&lt;/td&gt;&lt;td&gt;
  46. %parm[#4]%;&lt;/td&gt;&lt;td&gt;&lt;p&gt;
  47. normal(0)
  48. noComm(1)
  49. fanFail(2)
  50. overTemp(3)
  51. &lt;/p&gt;&lt;/td&gt;&lt;/tr&gt;&lt;/table&gt;
  52. </descr>
  53. <logmsg dest='logndisplay'>&lt;p&gt;
  54. Sentry Event: towerStatus is now normal trap received
  55. systemLocation=%parm[#1]%
  56. towerID=%parm[#2]%
  57. towerName=%parm[#3]%
  58. </logmsg>
  59. <severity>Normal</severity>
  60. <alarm-data reduction-key="%uei%:%dpname%:%nodeid%:%interface%:%parm[#2]%:%parm[#3]%" alarm-type="2" clear-key="uei.opennms.org/vendor/ServerTech/traps/towerStatusEvent-Error:%dpname%:%nodeid%:%interface%:%parm[#2]%i:%parm[#3]%" auto-clean="false"/>
  61. </event>
  62. <event>
  63. <mask>
  64. <maskelement>
  65. <mename>id</mename>
  66. <mevalue>.1.3.6.1.4.1.1718.3.100</mevalue>
  67. </maskelement>
  68. <maskelement>
  69. <mename>generic</mename>
  70. <mevalue>6</mevalue>
  71. </maskelement>
  72. <maskelement>
  73. <mename>specific</mename>
  74. <mevalue>1</mevalue>
  75. </maskelement>
  76. <varbind>
  77. <vbnumber>4</vbnumber>
  78. <vbvalue>1</vbvalue>
  79. </varbind>
  80. </mask>
  81. <uei>uei.opennms.org/vendor/ServerTech/traps/towerStatusEvent-Error</uei>
  82. <event-label>Sentry3-MIB defined trap event: towerStatusEvent-Error</event-label>
  83. <descr>
  84. &lt;p&gt;Tower status event. If enabled, this trap is sent when the
  85. towerStatus indicates an error state ('noComm', 'fanFail',
  86. or 'overTemp'). This trap is repeated periodically while the
  87. towerStatus remains in an error state. If the towerStatus
  88. returns to a non-error state ('normal'), this trap is sent
  89. once more with the non-error towerStatus, and then stops
  90. being repeated.
  91. While the towerStatus indicates a 'noComm' error state, all
  92. status and load traps are suppressed for input feeds and
  93. outlets on the tower.&lt;/p&gt;&lt;table&gt;
  94. &lt;tr&gt;&lt;td&gt;&lt;b&gt;
  95. systemLocation&lt;/b&gt;&lt;/td&gt;&lt;td&gt;
  96. %parm[#1]%;&lt;/td&gt;&lt;td&gt;&lt;p&gt;&lt;/p&gt;&lt;/td&gt;&lt;/tr&gt;
  97. &lt;tr&gt;&lt;td&gt;&lt;b&gt;
  98. towerID&lt;/b&gt;&lt;/td&gt;&lt;td&gt;
  99. %parm[#2]%;&lt;/td&gt;&lt;td&gt;&lt;p&gt;&lt;/p&gt;&lt;/td&gt;&lt;/tr&gt;
  100. &lt;tr&gt;&lt;td&gt;&lt;b&gt;
  101. towerName&lt;/b&gt;&lt;/td&gt;&lt;td&gt;
  102. %parm[#3]%;&lt;/td&gt;&lt;td&gt;&lt;p&gt;&lt;/p&gt;&lt;/td&gt;&lt;/tr&gt;
  103. &lt;tr&gt;&lt;td&gt;&lt;b&gt;
  104. towerStatus&lt;/b&gt;&lt;/td&gt;&lt;td&gt;
  105. %parm[#4]%;&lt;/td&gt;&lt;td&gt;&lt;p&gt;
  106. normal(0)
  107. noComm(1)
  108. fanFail(2)
  109. overTemp(3)
  110. &lt;/p&gt;&lt;/td&gt;&lt;/tr&gt;&lt;/table&gt;
  111. </descr>
  112. <logmsg dest='logndisplay'>&lt;p&gt;
  113. Sentry Event: towerStatus comm failure trap received
  114. systemLocation=%parm[#1]%
  115. towerID=%parm[#2]%
  116. towerName=%parm[#3]%
  117. </logmsg>
  118. <severity>Minor</severity>
  119. <alarm-data reduction-key="%uei%:%dpname%:%nodeid%:%interface%:%parm[#2]%:%parm[#3]%" alarm-type="1" auto-clean="false"/>
  120. </event>
  121. <event>
  122. <mask>
  123. <maskelement>
  124. <mename>id</mename>
  125. <mevalue>.1.3.6.1.4.1.1718.3.100</mevalue>
  126. </maskelement>
  127. <maskelement>
  128. <mename>generic</mename>
  129. <mevalue>6</mevalue>
  130. </maskelement>
  131. <maskelement>
  132. <mename>specific</mename>
  133. <mevalue>1</mevalue>
  134. </maskelement>
  135. <varbind>
  136. <vbnumber>4</vbnumber>
  137. <vbvalue>2</vbvalue>
  138. </varbind>
  139. </mask>
  140. <uei>uei.opennms.org/vendor/ServerTech/traps/towerStatusEvent-Error</uei>
  141. <event-label>Sentry3-MIB defined trap event: towerStatusEvent-Error</event-label>
  142. <descr>
  143. &lt;p&gt;Tower status event. If enabled, this trap is sent when the
  144. towerStatus indicates an error state ('noComm', 'fanFail',
  145. or 'overTemp'). This trap is repeated periodically while the
  146. towerStatus remains in an error state. If the towerStatus
  147. returns to a non-error state ('normal'), this trap is sent
  148. once more with the non-error towerStatus, and then stops
  149. being repeated.
  150. While the towerStatus indicates a 'noComm' error state, all
  151. status and load traps are suppressed for input feeds and
  152. outlets on the tower.&lt;/p&gt;&lt;table&gt;
  153. &lt;tr&gt;&lt;td&gt;&lt;b&gt;
  154. systemLocation&lt;/b&gt;&lt;/td&gt;&lt;td&gt;
  155. %parm[#1]%;&lt;/td&gt;&lt;td&gt;&lt;p&gt;&lt;/p&gt;&lt;/td&gt;&lt;/tr&gt;
  156. &lt;tr&gt;&lt;td&gt;&lt;b&gt;
  157. towerID&lt;/b&gt;&lt;/td&gt;&lt;td&gt;
  158. %parm[#2]%;&lt;/td&gt;&lt;td&gt;&lt;p&gt;&lt;/p&gt;&lt;/td&gt;&lt;/tr&gt;
  159. &lt;tr&gt;&lt;td&gt;&lt;b&gt;
  160. towerName&lt;/b&gt;&lt;/td&gt;&lt;td&gt;
  161. %parm[#3]%;&lt;/td&gt;&lt;td&gt;&lt;p&gt;&lt;/p&gt;&lt;/td&gt;&lt;/tr&gt;
  162. &lt;tr&gt;&lt;td&gt;&lt;b&gt;
  163. towerStatus&lt;/b&gt;&lt;/td&gt;&lt;td&gt;
  164. %parm[#4]%;&lt;/td&gt;&lt;td&gt;&lt;p&gt;
  165. normal(0)
  166. noComm(1)
  167. fanFail(2)
  168. overTemp(3)
  169. &lt;/p&gt;&lt;/td&gt;&lt;/tr&gt;&lt;/table&gt;
  170. </descr>
  171. <logmsg dest='logndisplay'>&lt;p&gt;
  172. Sentry Event: towerStatus fan failure trap received
  173. systemLocation=%parm[#1]%
  174. towerID=%parm[#2]%
  175. towerName=%parm[#3]%
  176. </logmsg>
  177. <severity>Major</severity>
  178. <alarm-data reduction-key="%uei%:%dpname%:%nodeid%:%interface%:%parm[#2]%:%parm[#3]%" alarm-type="1" auto-clean="false"/>
  179. </event>
  180. <event>
  181. <mask>
  182. <maskelement>
  183. <mename>id</mename>
  184. <mevalue>.1.3.6.1.4.1.1718.3.100</mevalue>
  185. </maskelement>
  186. <maskelement>
  187. <mename>generic</mename>
  188. <mevalue>6</mevalue>
  189. </maskelement>
  190. <maskelement>
  191. <mename>specific</mename>
  192. <mevalue>3</mevalue>
  193. </maskelement>
  194. <varbind>
  195. <vbnumber>4</vbnumber>
  196. <vbvalue>1</vbvalue>
  197. </varbind>
  198. </mask>
  199. <uei>uei.opennms.org/vendor/ServerTech/traps/towerStatusEvent-Error</uei>
  200. <event-label>Sentry3-MIB defined trap event: towerStatusEvent-Error</event-label>
  201. <descr>
  202. &lt;p&gt;Tower status event. If enabled, this trap is sent when the
  203. towerStatus indicates an error state ('noComm', 'fanFail',
  204. or 'overTemp'). This trap is repeated periodically while the
  205. towerStatus remains in an error state. If the towerStatus
  206. returns to a non-error state ('normal'), this trap is sent
  207. once more with the non-error towerStatus, and then stops
  208. being repeated.
  209. While the towerStatus indicates a 'noComm' error state, all
  210. status and load traps are suppressed for input feeds and
  211. outlets on the tower.&lt;/p&gt;&lt;table&gt;
  212. &lt;tr&gt;&lt;td&gt;&lt;b&gt;
  213. systemLocation&lt;/b&gt;&lt;/td&gt;&lt;td&gt;
  214. %parm[#1]%;&lt;/td&gt;&lt;td&gt;&lt;p&gt;&lt;/p&gt;&lt;/td&gt;&lt;/tr&gt;
  215. &lt;tr&gt;&lt;td&gt;&lt;b&gt;
  216. towerID&lt;/b&gt;&lt;/td&gt;&lt;td&gt;
  217. %parm[#2]%;&lt;/td&gt;&lt;td&gt;&lt;p&gt;&lt;/p&gt;&lt;/td&gt;&lt;/tr&gt;
  218. &lt;tr&gt;&lt;td&gt;&lt;b&gt;
  219. towerName&lt;/b&gt;&lt;/td&gt;&lt;td&gt;
  220. %parm[#3]%;&lt;/td&gt;&lt;td&gt;&lt;p&gt;&lt;/p&gt;&lt;/td&gt;&lt;/tr&gt;
  221. &lt;tr&gt;&lt;td&gt;&lt;b&gt;
  222. towerStatus&lt;/b&gt;&lt;/td&gt;&lt;td&gt;
  223. %parm[#4]%;&lt;/td&gt;&lt;td&gt;&lt;p&gt;
  224. normal(0)
  225. noComm(1)
  226. fanFail(2)
  227. overTemp(3)
  228. &lt;/p&gt;&lt;/td&gt;&lt;/tr&gt;&lt;/table&gt;
  229. </descr>
  230. <logmsg dest='logndisplay'>&lt;p&gt;
  231. Sentry Event: towerStatus over temperature trap received
  232. systemLocation=%parm[#1]%
  233. towerID=%parm[#2]%
  234. towerName=%parm[#3]%
  235. </logmsg>
  236. <severity>Major</severity>
  237. <alarm-data reduction-key="%uei%:%dpname%:%nodeid%:%interface%:%parm[#2]%:%parm[#3]%" alarm-type="1" auto-clean="false"/>
  238. </event>
  239. <event>
  240. <mask>
  241. <maskelement>
  242. <mename>id</mename>
  243. <mevalue>.1.3.6.1.4.1.1718.3.100</mevalue>
  244. </maskelement>
  245. <maskelement>
  246. <mename>generic</mename>
  247. <mevalue>6</mevalue>
  248. </maskelement>
  249. <maskelement>
  250. <mename>specific</mename>
  251. <mevalue>1</mevalue>
  252. </maskelement>
  253. </mask>
  254. <uei>uei.opennms.org/vendor/ServerTech/traps/towerStatusEvent</uei>
  255. <event-label>Sentry3-MIB defined trap event: towerStatusEvent</event-label>
  256. <descr>
  257. &lt;p&gt;Tower status event. If enabled, this trap is sent when the
  258. towerStatus indicates an error state ('noComm', 'fanFail',
  259. or 'overTemp'). This trap is repeated periodically while the
  260. towerStatus remains in an error state. If the towerStatus
  261. returns to a non-error state ('normal'), this trap is sent
  262. once more with the non-error towerStatus, and then stops
  263. being repeated.
  264. While the towerStatus indicates a 'noComm' error state, all
  265. status and load traps are suppressed for input feeds and
  266. outlets on the tower.&lt;/p&gt;&lt;table&gt;
  267. &lt;tr&gt;&lt;td&gt;&lt;b&gt;
  268. systemLocation&lt;/b&gt;&lt;/td&gt;&lt;td&gt;
  269. %parm[#1]%;&lt;/td&gt;&lt;td&gt;&lt;p&gt;&lt;/p&gt;&lt;/td&gt;&lt;/tr&gt;
  270. &lt;tr&gt;&lt;td&gt;&lt;b&gt;
  271. towerID&lt;/b&gt;&lt;/td&gt;&lt;td&gt;
  272. %parm[#2]%;&lt;/td&gt;&lt;td&gt;&lt;p&gt;&lt;/p&gt;&lt;/td&gt;&lt;/tr&gt;
  273. &lt;tr&gt;&lt;td&gt;&lt;b&gt;
  274. towerName&lt;/b&gt;&lt;/td&gt;&lt;td&gt;
  275. %parm[#3]%;&lt;/td&gt;&lt;td&gt;&lt;p&gt;&lt;/p&gt;&lt;/td&gt;&lt;/tr&gt;
  276. &lt;tr&gt;&lt;td&gt;&lt;b&gt;
  277. towerStatus&lt;/b&gt;&lt;/td&gt;&lt;td&gt;
  278. %parm[#4]%;&lt;/td&gt;&lt;td&gt;&lt;p&gt;
  279. normal(0)
  280. noComm(1)
  281. fanFail(2)
  282. overTemp(3)
  283. &lt;/p&gt;&lt;/td&gt;&lt;/tr&gt;&lt;/table&gt;
  284. </descr>
  285. <logmsg dest='logndisplay'>&lt;p&gt;
  286. Sentry Event: towerStatusEvent trap received
  287. systemLocation=%parm[#1]%
  288. towerID=%parm[#2]%
  289. towerName=%parm[#3]%
  290. towerStatus=%parm[#4]%&lt;/p&gt;
  291. </logmsg>
  292. <severity>Indeterminate</severity>
  293. </event>
  294. <event>
  295. <mask>
  296. <maskelement>
  297. <mename>id</mename>
  298. <mevalue>.1.3.6.1.4.1.1718.3.100</mevalue>
  299. </maskelement>
  300. <maskelement>
  301. <mename>generic</mename>
  302. <mevalue>6</mevalue>
  303. </maskelement>
  304. <maskelement>
  305. <mename>specific</mename>
  306. <mevalue>2</mevalue>
  307. </maskelement>
  308. <varbind>
  309. <vbnumber>4</vbnumber>
  310. <vbvalue>0</vbvalue>
  311. </varbind>
  312. </mask>
  313. <uei>uei.opennms.org/vendor/ServerTech/traps/infeedStatusEvent-Normal</uei>
  314. <event-label>Sentry3-MIB defined trap event: infeedStatusEvent-Normal</event-label>
  315. <descr>
  316. &lt;p&gt;Input feed status event. If enabled, this trap is sent when
  317. the infeedStatus indicates an error state ('offError',
  318. 'onError', or 'noComm'). This trap is repeated periodically
  319. while the infeedStatus remains in an error state. If the
  320. infeedStatus returns to a non-error state ('off' or 'on'),
  321. this trap is sent once more with the non-error infeedStatus,
  322. and then stops being repeated.
  323. While the infeedStatus indicates an error state, load
  324. traps are suppressed for the input feed, and, if the
  325. infeedCapabilities 'failSafe' bit is FALSE, all status and
  326. load traps are suppressed for outlets on the input feed.&lt;/p&gt;&lt;table&gt;
  327. &lt;tr&gt;&lt;td&gt;&lt;b&gt;
  328. systemLocation&lt;/b&gt;&lt;/td&gt;&lt;td&gt;
  329. %parm[#1]%;&lt;/td&gt;&lt;td&gt;&lt;p&gt;&lt;/p&gt;&lt;/td&gt;&lt;/tr&gt;
  330. &lt;tr&gt;&lt;td&gt;&lt;b&gt;
  331. infeedID&lt;/b&gt;&lt;/td&gt;&lt;td&gt;
  332. %parm[#2]%;&lt;/td&gt;&lt;td&gt;&lt;p&gt;&lt;/p&gt;&lt;/td&gt;&lt;/tr&gt;
  333. &lt;tr&gt;&lt;td&gt;&lt;b&gt;
  334. infeedName&lt;/b&gt;&lt;/td&gt;&lt;td&gt;
  335. %parm[#3]%;&lt;/td&gt;&lt;td&gt;&lt;p&gt;&lt;/p&gt;&lt;/td&gt;&lt;/tr&gt;
  336. &lt;tr&gt;&lt;td&gt;&lt;b&gt;
  337. infeedStatus&lt;/b&gt;&lt;/td&gt;&lt;td&gt;
  338. %parm[#4]%;&lt;/td&gt;&lt;td&gt;&lt;p&gt;
  339. off(0)
  340. on(1)
  341. offWait(2)
  342. onWait(3)
  343. offError(4)
  344. onError(5)
  345. noComm(6)
  346. &lt;/p&gt;&lt;/td&gt;&lt;/tr&gt;&lt;/table&gt;
  347. </descr>
  348. <logmsg dest='logndisplay'>&lt;p&gt;
  349. Sentry Event: Input Feed Status off (normal)
  350. systemLocation=%parm[#1]%
  351. infeedID=%parm[#2]%
  352. infeedName=%parm[#3]%
  353. </logmsg>
  354. <severity>Normal</severity>
  355. <alarm-data reduction-key="%uei%:%dpname%:%nodeid%:%interface%:%parm[#2]%:%parm[#3]%" alarm-type="2" clear-key="uei.opennms.org/vendor/ServerTech/traps/infeedStatusEvent-Error:%dpname%:%nodeid%:%interface%:%parm[#2]%i:%parm[#3]%" auto-clean="false"/>
  356. </event>
  357. <event>
  358. <mask>
  359. <maskelement>
  360. <mename>id</mename>
  361. <mevalue>.1.3.6.1.4.1.1718.3.100</mevalue>
  362. </maskelement>
  363. <maskelement>
  364. <mename>generic</mename>
  365. <mevalue>6</mevalue>
  366. </maskelement>
  367. <maskelement>
  368. <mename>specific</mename>
  369. <mevalue>2</mevalue>
  370. </maskelement>
  371. <varbind>
  372. <vbnumber>4</vbnumber>
  373. <vbvalue>1</vbvalue>
  374. </varbind>
  375. </mask>
  376. <uei>uei.opennms.org/vendor/ServerTech/traps/infeedStatusEvent-Normal</uei>
  377. <event-label>Sentry3-MIB defined trap event: infeedStatusEvent-Normal</event-label>
  378. <descr>
  379. &lt;p&gt;Input feed status event. If enabled, this trap is sent when
  380. the infeedStatus indicates an error state ('offError',
  381. 'onError', or 'noComm'). This trap is repeated periodically
  382. while the infeedStatus remains in an error state. If the
  383. infeedStatus returns to a non-error state ('off' or 'on'),
  384. this trap is sent once more with the non-error infeedStatus,
  385. and then stops being repeated.
  386. While the infeedStatus indicates an error state, load
  387. traps are suppressed for the input feed, and, if the
  388. infeedCapabilities 'failSafe' bit is FALSE, all status and
  389. load traps are suppressed for outlets on the input feed.&lt;/p&gt;&lt;table&gt;
  390. &lt;tr&gt;&lt;td&gt;&lt;b&gt;
  391. systemLocation&lt;/b&gt;&lt;/td&gt;&lt;td&gt;
  392. %parm[#1]%;&lt;/td&gt;&lt;td&gt;&lt;p&gt;&lt;/p&gt;&lt;/td&gt;&lt;/tr&gt;
  393. &lt;tr&gt;&lt;td&gt;&lt;b&gt;
  394. infeedID&lt;/b&gt;&lt;/td&gt;&lt;td&gt;
  395. %parm[#2]%;&lt;/td&gt;&lt;td&gt;&lt;p&gt;&lt;/p&gt;&lt;/td&gt;&lt;/tr&gt;
  396. &lt;tr&gt;&lt;td&gt;&lt;b&gt;
  397. infeedName&lt;/b&gt;&lt;/td&gt;&lt;td&gt;
  398. %parm[#3]%;&lt;/td&gt;&lt;td&gt;&lt;p&gt;&lt;/p&gt;&lt;/td&gt;&lt;/tr&gt;
  399. &lt;tr&gt;&lt;td&gt;&lt;b&gt;
  400. infeedStatus&lt;/b&gt;&lt;/td&gt;&lt;td&gt;
  401. %parm[#4]%;&lt;/td&gt;&lt;td&gt;&lt;p&gt;
  402. off(0)
  403. on(1)
  404. offWait(2)
  405. onWait(3)
  406. offError(4)
  407. onError(5)
  408. noComm(6)
  409. &lt;/p&gt;&lt;/td&gt;&lt;/tr&gt;&lt;/table&gt;
  410. </descr>
  411. <logmsg dest='logndisplay'>&lt;p&gt;
  412. Sentry Event: Input Feed Status on (normal)
  413. systemLocation=%parm[#1]%
  414. infeedID=%parm[#2]%
  415. infeedName=%parm[#3]%
  416. </logmsg>
  417. <severity>Normal</severity>
  418. <alarm-data reduction-key="%uei%:%dpname%:%nodeid%:%interface%:%parm[#2]%:%parm[#3]%" alarm-type="2" clear-key="uei.opennms.org/vendor/ServerTech/traps/infeedStatusEvent-Error:%dpname%:%nodeid%:%interface%:%parm[#2]%i:%parm[#3]%" auto-clean="false"/>
  419. </event>
  420. <event>
  421. <mask>
  422. <maskelement>
  423. <mename>id</mename>
  424. <mevalue>.1.3.6.1.4.1.1718.3.100</mevalue>
  425. </maskelement>
  426. <maskelement>
  427. <mename>generic</mename>
  428. <mevalue>6</mevalue>
  429. </maskelement>
  430. <maskelement>
  431. <mename>specific</mename>
  432. <mevalue>2</mevalue>
  433. </maskelement>
  434. <varbind>
  435. <vbnumber>4</vbnumber>
  436. <vbvalue>2</vbvalue>
  437. </varbind>
  438. </mask>
  439. <uei>uei.opennms.org/vendor/ServerTech/traps/infeedStatusEvent-Error</uei>
  440. <event-label>Sentry3-MIB defined trap event: infeedStatusEvent-Error</event-label>
  441. <descr>
  442. &lt;p&gt;Input feed status event. If enabled, this trap is sent when
  443. the infeedStatus indicates an error state ('offError',
  444. 'onError', or 'noComm'). This trap is repeated periodically
  445. while the infeedStatus remains in an error state. If the
  446. infeedStatus returns to a non-error state ('off' or 'on'),
  447. this trap is sent once more with the non-error infeedStatus,
  448. and then stops being repeated.
  449. While the infeedStatus indicates an error state, load
  450. traps are suppressed for the input feed, and, if the
  451. infeedCapabilities 'failSafe' bit is FALSE, all status and
  452. load traps are suppressed for outlets on the input feed.&lt;/p&gt;&lt;table&gt;
  453. &lt;tr&gt;&lt;td&gt;&lt;b&gt;
  454. systemLocation&lt;/b&gt;&lt;/td&gt;&lt;td&gt;
  455. %parm[#1]%;&lt;/td&gt;&lt;td&gt;&lt;p&gt;&lt;/p&gt;&lt;/td&gt;&lt;/tr&gt;
  456. &lt;tr&gt;&lt;td&gt;&lt;b&gt;
  457. infeedID&lt;/b&gt;&lt;/td&gt;&lt;td&gt;
  458. %parm[#2]%;&lt;/td&gt;&lt;td&gt;&lt;p&gt;&lt;/p&gt;&lt;/td&gt;&lt;/tr&gt;
  459. &lt;tr&gt;&lt;td&gt;&lt;b&gt;
  460. infeedName&lt;/b&gt;&lt;/td&gt;&lt;td&gt;
  461. %parm[#3]%;&lt;/td&gt;&lt;td&gt;&lt;p&gt;&lt;/p&gt;&lt;/td&gt;&lt;/tr&gt;
  462. &lt;tr&gt;&lt;td&gt;&lt;b&gt;
  463. infeedStatus&lt;/b&gt;&lt;/td&gt;&lt;td&gt;
  464. %parm[#4]%;&lt;/td&gt;&lt;td&gt;&lt;p&gt;
  465. off(0)
  466. on(1)
  467. offWait(2)
  468. onWait(3)
  469. offError(4)
  470. onError(5)
  471. noComm(6)
  472. &lt;/p&gt;&lt;/td&gt;&lt;/tr&gt;&lt;/table&gt;
  473. </descr>
  474. <logmsg dest='logndisplay'>&lt;p&gt;
  475. Sentry Event: Input Feed Status offWait (error)
  476. systemLocation=%parm[#1]%
  477. infeedID=%parm[#2]%
  478. infeedName=%parm[#3]%
  479. </logmsg>
  480. <severity>Minor</severity>
  481. <alarm-data reduction-key="%uei%:%dpname%:%nodeid%:%interface%:%parm[#2]%:%parm[#3]%" alarm-type="1" auto-clean="false"/>
  482. </event>
  483. <event>
  484. <mask>
  485. <maskelement>
  486. <mename>id</mename>
  487. <mevalue>.1.3.6.1.4.1.1718.3.100</mevalue>
  488. </maskelement>
  489. <maskelement>
  490. <mename>generic</mename>
  491. <mevalue>6</mevalue>
  492. </maskelement>
  493. <maskelement>
  494. <mename>specific</mename>
  495. <mevalue>2</mevalue>
  496. </maskelement>
  497. <varbind>
  498. <vbnumber>4</vbnumber>
  499. <vbvalue>3</vbvalue>
  500. </varbind>
  501. </mask>
  502. <uei>uei.opennms.org/vendor/ServerTech/traps/infeedStatusEvent-Error</uei>
  503. <event-label>Sentry3-MIB defined trap event: infeedStatusEvent-Error</event-label>
  504. <descr>
  505. &lt;p&gt;Input feed status event. If enabled, this trap is sent when
  506. the infeedStatus indicates an error state ('offError',
  507. 'onError', or 'noComm'). This trap is repeated periodically
  508. while the infeedStatus remains in an error state. If the
  509. infeedStatus returns to a non-error state ('off' or 'on'),
  510. this trap is sent once more with the non-error infeedStatus,
  511. and then stops being repeated.
  512. While the infeedStatus indicates an error state, load
  513. traps are suppressed for the input feed, and, if the
  514. infeedCapabilities 'failSafe' bit is FALSE, all status and
  515. load traps are suppressed for outlets on the input feed.&lt;/p&gt;&lt;table&gt;
  516. &lt;tr&gt;&lt;td&gt;&lt;b&gt;
  517. systemLocation&lt;/b&gt;&lt;/td&gt;&lt;td&gt;
  518. %parm[#1]%;&lt;/td&gt;&lt;td&gt;&lt;p&gt;&lt;/p&gt;&lt;/td&gt;&lt;/tr&gt;
  519. &lt;tr&gt;&lt;td&gt;&lt;b&gt;
  520. infeedID&lt;/b&gt;&lt;/td&gt;&lt;td&gt;
  521. %parm[#2]%;&lt;/td&gt;&lt;td&gt;&lt;p&gt;&lt;/p&gt;&lt;/td&gt;&lt;/tr&gt;
  522. &lt;tr&gt;&lt;td&gt;&lt;b&gt;
  523. infeedName&lt;/b&gt;&lt;/td&gt;&lt;td&gt;
  524. %parm[#3]%;&lt;/td&gt;&lt;td&gt;&lt;p&gt;&lt;/p&gt;&lt;/td&gt;&lt;/tr&gt;
  525. &lt;tr&gt;&lt;td&gt;&lt;b&gt;
  526. infeedStatus&lt;/b&gt;&lt;/td&gt;&lt;td&gt;
  527. %parm[#4]%;&lt;/td&gt;&lt;td&gt;&lt;p&gt;
  528. off(0)
  529. on(1)
  530. offWait(2)
  531. onWait(3)
  532. offError(4)
  533. onError(5)
  534. noComm(6)
  535. &lt;/p&gt;&lt;/td&gt;&lt;/tr&gt;&lt;/table&gt;
  536. </descr>
  537. <logmsg dest='logndisplay'>&lt;p&gt;
  538. Sentry Event: Input Feed Status onWait (error)
  539. systemLocation=%parm[#1]%
  540. infeedID=%parm[#2]%
  541. infeedName=%parm[#3]%
  542. </logmsg>
  543. <severity>Minor</severity>
  544. <alarm-data reduction-key="%uei%:%dpname%:%nodeid%:%interface%:%parm[#2]%:%parm[#3]%" alarm-type="1" auto-clean="false"/>
  545. </event>
  546. <event>
  547. <mask>
  548. <maskelement>
  549. <mename>id</mename>
  550. <mevalue>.1.3.6.1.4.1.1718.3.100</mevalue>
  551. </maskelement>
  552. <maskelement>
  553. <mename>generic</mename>
  554. <mevalue>6</mevalue>
  555. </maskelement>
  556. <maskelement>
  557. <mename>specific</mename>
  558. <mevalue>2</mevalue>
  559. </maskelement>
  560. <varbind>
  561. <vbnumber>4</vbnumber>
  562. <vbvalue>4</vbvalue>
  563. </varbind>
  564. </mask>
  565. <uei>uei.opennms.org/vendor/ServerTech/traps/infeedStatusEvent-Error</uei>
  566. <event-label>Sentry3-MIB defined trap event: infeedStatusEvent-Error</event-label>
  567. <descr>
  568. &lt;p&gt;Input feed status event. If enabled, this trap is sent when
  569. the infeedStatus indicates an error state ('offError',
  570. 'onError', or 'noComm'). This trap is repeated periodically
  571. while the infeedStatus remains in an error state. If the
  572. infeedStatus returns to a non-error state ('off' or 'on'),
  573. this trap is sent once more with the non-error infeedStatus,
  574. and then stops being repeated.
  575. While the infeedStatus indicates an error state, load
  576. traps are suppressed for the input feed, and, if the
  577. infeedCapabilities 'failSafe' bit is FALSE, all status and
  578. load traps are suppressed for outlets on the input feed.&lt;/p&gt;&lt;table&gt;
  579. &lt;tr&gt;&lt;td&gt;&lt;b&gt;
  580. systemLocation&lt;/b&gt;&lt;/td&gt;&lt;td&gt;
  581. %parm[#1]%;&lt;/td&gt;&lt;td&gt;&lt;p&gt;&lt;/p&gt;&lt;/td&gt;&lt;/tr&gt;
  582. &lt;tr&gt;&lt;td&gt;&lt;b&gt;
  583. infeedID&lt;/b&gt;&lt;/td&gt;&lt;td&gt;
  584. %parm[#2]%;&lt;/td&gt;&lt;td&gt;&lt;p&gt;&lt;/p&gt;&lt;/td&gt;&lt;/tr&gt;
  585. &lt;tr&gt;&lt;td&gt;&lt;b&gt;
  586. infeedName&lt;/b&gt;&lt;/td&gt;&lt;td&gt;
  587. %parm[#3]%;&lt;/td&gt;&lt;td&gt;&lt;p&gt;&lt;/p&gt;&lt;/td&gt;&lt;/tr&gt;
  588. &lt;tr&gt;&lt;td&gt;&lt;b&gt;
  589. infeedStatus&lt;/b&gt;&lt;/td&gt;&lt;td&gt;
  590. %parm[#4]%;&lt;/td&gt;&lt;td&gt;&lt;p&gt;
  591. off(0)
  592. on(1)
  593. offWait(2)
  594. onWait(3)
  595. offError(4)
  596. onError(5)
  597. noComm(6)
  598. &lt;/p&gt;&lt;/td&gt;&lt;/tr&gt;&lt;/table&gt;
  599. </descr>
  600. <logmsg dest='logndisplay'>&lt;p&gt;
  601. Sentry Event: Input Feed Status offError (error)
  602. systemLocation=%parm[#1]%
  603. infeedID=%parm[#2]%
  604. infeedName=%parm[#3]%
  605. </logmsg>
  606. <severity>Minor</severity>
  607. <alarm-data reduction-key="%uei%:%dpname%:%nodeid%:%interface%:%parm[#2]%:%parm[#3]%" alarm-type="1" auto-clean="false"/>
  608. </event>
  609. <event>
  610. <mask>
  611. <maskelement>
  612. <mename>id</mename>
  613. <mevalue>.1.3.6.1.4.1.1718.3.100</mevalue>
  614. </maskelement>
  615. <maskelement>
  616. <mename>generic</mename>
  617. <mevalue>6</mevalue>
  618. </maskelement>
  619. <maskelement>
  620. <mename>specific</mename>
  621. <mevalue>2</mevalue>
  622. </maskelement>
  623. <varbind>
  624. <vbnumber>4</vbnumber>
  625. <vbvalue>5</vbvalue>
  626. </varbind>
  627. </mask>
  628. <uei>uei.opennms.org/vendor/ServerTech/traps/infeedStatusEvent-Error</uei>
  629. <event-label>Sentry3-MIB defined trap event: infeedStatusEvent-Error</event-label>
  630. <descr>
  631. &lt;p&gt;Input feed status event. If enabled, this trap is sent when
  632. the infeedStatus indicates an error state ('offError',
  633. 'onError', or 'noComm'). This trap is repeated periodically
  634. while the infeedStatus remains in an error state. If the
  635. infeedStatus returns to a non-error state ('off' or 'on'),
  636. this trap is sent once more with the non-error infeedStatus,
  637. and then stops being repeated.
  638. While the infeedStatus indicates an error state, load
  639. traps are suppressed for the input feed, and, if the
  640. infeedCapabilities 'failSafe' bit is FALSE, all status and
  641. load traps are suppressed for outlets on the input feed.&lt;/p&gt;&lt;table&gt;
  642. &lt;tr&gt;&lt;td&gt;&lt;b&gt;
  643. systemLocation&lt;/b&gt;&lt;/td&gt;&lt;td&gt;
  644. %parm[#1]%;&lt;/td&gt;&lt;td&gt;&lt;p&gt;&lt;/p&gt;&lt;/td&gt;&lt;/tr&gt;
  645. &lt;tr&gt;&lt;td&gt;&lt;b&gt;
  646. infeedID&lt;/b&gt;&lt;/td&gt;&lt;td&gt;
  647. %parm[#2]%;&lt;/td&gt;&lt;td&gt;&lt;p&gt;&lt;/p&gt;&lt;/td&gt;&lt;/tr&gt;
  648. &lt;tr&gt;&lt;td&gt;&lt;b&gt;
  649. infeedName&lt;/b&gt;&lt;/td&gt;&lt;td&gt;
  650. %parm[#3]%;&lt;/td&gt;&lt;td&gt;&lt;p&gt;&lt;/p&gt;&lt;/td&gt;&lt;/tr&gt;
  651. &lt;tr&gt;&lt;td&gt;&lt;b&gt;
  652. infeedStatus&lt;/b&gt;&lt;/td&gt;&lt;td&gt;
  653. %parm[#4]%;&lt;/td&gt;&lt;td&gt;&lt;p&gt;
  654. off(0)
  655. on(1)
  656. offWait(2)
  657. onWait(3)
  658. offError(4)
  659. onError(5)
  660. noComm(6)
  661. &lt;/p&gt;&lt;/td&gt;&lt;/tr&gt;&lt;/table&gt;
  662. </descr>
  663. <logmsg dest='logndisplay'>&lt;p&gt;
  664. Sentry Event: Input Feed Status onError (error)
  665. systemLocation=%parm[#1]%
  666. infeedID=%parm[#2]%
  667. infeedName=%parm[#3]%
  668. </logmsg>
  669. <severity>Minor</severity>
  670. <alarm-data reduction-key="%uei%:%dpname%:%nodeid%:%interface%:%parm[#2]%:%parm[#3]%" alarm-type="1" auto-clean="false"/>
  671. </event>
  672. <event>
  673. <mask>
  674. <maskelement>
  675. <mename>id</mename>
  676. <mevalue>.1.3.6.1.4.1.1718.3.100</mevalue>
  677. </maskelement>
  678. <maskelement>
  679. <mename>generic</mename>
  680. <mevalue>6</mevalue>
  681. </maskelement>
  682. <maskelement>
  683. <mename>specific</mename>
  684. <mevalue>2</mevalue>
  685. </maskelement>
  686. <varbind>
  687. <vbnumber>4</vbnumber>
  688. <vbvalue>6</vbvalue>
  689. </varbind>
  690. </mask>
  691. <uei>uei.opennms.org/vendor/ServerTech/traps/infeedStatusEvent-Error</uei>
  692. <event-label>Sentry3-MIB defined trap event: infeedStatusEvent-Error</event-label>
  693. <descr>
  694. &lt;p&gt;Input feed status event. If enabled, this trap is sent when
  695. the infeedStatus indicates an error state ('offError',
  696. 'onError', or 'noComm'). This trap is repeated periodically
  697. while the infeedStatus remains in an error state. If the
  698. infeedStatus returns to a non-error state ('off' or 'on'),
  699. this trap is sent once more with the non-error infeedStatus,
  700. and then stops being repeated.
  701. While the infeedStatus indicates an error state, load
  702. traps are suppressed for the input feed, and, if the
  703. infeedCapabilities 'failSafe' bit is FALSE, all status and
  704. load traps are suppressed for outlets on the input feed.&lt;/p&gt;&lt;table&gt;
  705. &lt;tr&gt;&lt;td&gt;&lt;b&gt;
  706. systemLocation&lt;/b&gt;&lt;/td&gt;&lt;td&gt;
  707. %parm[#1]%;&lt;/td&gt;&lt;td&gt;&lt;p&gt;&lt;/p&gt;&lt;/td&gt;&lt;/tr&gt;
  708. &lt;tr&gt;&lt;td&gt;&lt;b&gt;
  709. infeedID&lt;/b&gt;&lt;/td&gt;&lt;td&gt;
  710. %parm[#2]%;&lt;/td&gt;&lt;td&gt;&lt;p&gt;&lt;/p&gt;&lt;/td&gt;&lt;/tr&gt;
  711. &lt;tr&gt;&lt;td&gt;&lt;b&gt;
  712. infeedName&lt;/b&gt;&lt;/td&gt;&lt;td&gt;
  713. %parm[#3]%;&lt;/td&gt;&lt;td&gt;&lt;p&gt;&lt;/p&gt;&lt;/td&gt;&lt;/tr&gt;
  714. &lt;tr&gt;&lt;td&gt;&lt;b&gt;
  715. infeedStatus&lt;/b&gt;&lt;/td&gt;&lt;td&gt;
  716. %parm[#4]%;&lt;/td&gt;&lt;td&gt;&lt;p&gt;
  717. off(0)
  718. on(1)
  719. offWait(2)
  720. onWait(3)
  721. offError(4)
  722. onError(5)
  723. noComm(6)
  724. &lt;/p&gt;&lt;/td&gt;&lt;/tr&gt;&lt;/table&gt;
  725. </descr>
  726. <logmsg dest='logndisplay'>&lt;p&gt;
  727. Sentry Event: Input Feed Status noComm (error)
  728. systemLocation=%parm[#1]%
  729. infeedID=%parm[#2]%
  730. infeedName=%parm[#3]%
  731. </logmsg>
  732. <severity>Minor</severity>
  733. <alarm-data reduction-key="%uei%:%dpname%:%nodeid%:%interface%:%parm[#2]%:%parm[#3]%" alarm-type="1" auto-clean="false"/>
  734. </event>
  735. <event>
  736. <mask>
  737. <maskelement>
  738. <mename>id</mename>
  739. <mevalue>.1.3.6.1.4.1.1718.3.100</mevalue>
  740. </maskelement>
  741. <maskelement>
  742. <mename>generic</mename>
  743. <mevalue>6</mevalue>
  744. </maskelement>
  745. <maskelement>
  746. <mename>specific</mename>
  747. <mevalue>2</mevalue>
  748. </maskelement>
  749. </mask>
  750. <uei>uei.opennms.org/vendor/ServerTech/traps/infeedStatusEvent</uei>
  751. <event-label>Sentry3-MIB defined trap event: infeedStatusEvent</event-label>
  752. <descr>
  753. &lt;p&gt;Input feed status event. If enabled, this trap is sent when
  754. the infeedStatus indicates an error state ('offError',
  755. 'onError', or 'noComm'). This trap is repeated periodically
  756. while the infeedStatus remains in an error state. If the
  757. infeedStatus returns to a non-error state ('off' or 'on'),
  758. this trap is sent once more with the non-error infeedStatus,
  759. and then stops being repeated.
  760. While the infeedStatus indicates an error state, load
  761. traps are suppressed for the input feed, and, if the
  762. infeedCapabilities 'failSafe' bit is FALSE, all status and
  763. load traps are suppressed for outlets on the input feed.&lt;/p&gt;&lt;table&gt;
  764. &lt;tr&gt;&lt;td&gt;&lt;b&gt;
  765. systemLocation&lt;/b&gt;&lt;/td&gt;&lt;td&gt;
  766. %parm[#1]%;&lt;/td&gt;&lt;td&gt;&lt;p&gt;&lt;/p&gt;&lt;/td&gt;&lt;/tr&gt;
  767. &lt;tr&gt;&lt;td&gt;&lt;b&gt;
  768. infeedID&lt;/b&gt;&lt;/td&gt;&lt;td&gt;
  769. %parm[#2]%;&lt;/td&gt;&lt;td&gt;&lt;p&gt;&lt;/p&gt;&lt;/td&gt;&lt;/tr&gt;
  770. &lt;tr&gt;&lt;td&gt;&lt;b&gt;
  771. infeedName&lt;/b&gt;&lt;/td&gt;&lt;td&gt;
  772. %parm[#3]%;&lt;/td&gt;&lt;td&gt;&lt;p&gt;&lt;/p&gt;&lt;/td&gt;&lt;/tr&gt;
  773. &lt;tr&gt;&lt;td&gt;&lt;b&gt;
  774. infeedStatus&lt;/b&gt;&lt;/td&gt;&lt;td&gt;
  775. %parm[#4]%;&lt;/td&gt;&lt;td&gt;&lt;p&gt;
  776. off(0)
  777. on(1)
  778. offWait(2)
  779. onWait(3)
  780. offError(4)
  781. onError(5)
  782. noComm(6)
  783. &lt;/p&gt;&lt;/td&gt;&lt;/tr&gt;&lt;/table&gt;
  784. </descr>
  785. <logmsg dest='logndisplay'>&lt;p&gt;
  786. Sentry Event: infeedStatusEvent trap received
  787. systemLocation=%parm[#1]%
  788. infeedID=%parm[#2]%
  789. infeedName=%parm[#3]%
  790. </logmsg>
  791. <severity>Indeterminate</severity>
  792. </event>
  793. <event>
  794. <mask>
  795. <maskelement>
  796. <mename>id</mename>
  797. <mevalue>.1.3.6.1.4.1.1718.3.100</mevalue>
  798. </maskelement>
  799. <maskelement>
  800. <mename>generic</mename>
  801. <mevalue>6</mevalue>
  802. </maskelement>
  803. <maskelement>
  804. <mename>specific</mename>
  805. <mevalue>3</mevalue>
  806. </maskelement>
  807. <varbind>
  808. <vbnumber>4</vbnumber>
  809. <vbvalue>0</vbvalue>
  810. </varbind>
  811. </mask>
  812. <uei>uei.opennms.org/vendor/ServerTech/traps/infeedLoadEvent-Normal</uei>
  813. <event-label>Sentry3-MIB defined trap event: infeedLoadEvent-Normal</event-label>
  814. <descr>
  815. &lt;p&gt;Input feed load event. If enabled, this trap is sent when
  816. the infeedLoadStatus indicates an error state ('loadLow',
  817. 'loadHigh', 'overLoad', 'readError', or 'noComm'). This
  818. trap is repeated periodically while the infeedLoadStatus
  819. remains in an error state. If the infeedLoadStatus returns
  820. to a non-error state ('normal' or 'notOn'), this trap is
  821. sent once more with the non-error infeedLoadStatus, and then
  822. stops being repeated.&lt;/p&gt;&lt;table&gt;
  823. &lt;tr&gt;&lt;td&gt;&lt;b&gt;
  824. systemLocation&lt;/b&gt;&lt;/td&gt;&lt;td&gt;
  825. %parm[#1]%;&lt;/td&gt;&lt;td&gt;&lt;p&gt;&lt;/p&gt;&lt;/td&gt;&lt;/tr&gt;
  826. &lt;tr&gt;&lt;td&gt;&lt;b&gt;
  827. infeedID&lt;/b&gt;&lt;/td&gt;&lt;td&gt;
  828. %parm[#2]%;&lt;/td&gt;&lt;td&gt;&lt;p&gt;&lt;/p&gt;&lt;/td&gt;&lt;/tr&gt;
  829. &lt;tr&gt;&lt;td&gt;&lt;b&gt;
  830. infeedName&lt;/b&gt;&lt;/td&gt;&lt;td&gt;
  831. %parm[#3]%;&lt;/td&gt;&lt;td&gt;&lt;p&gt;&lt;/p&gt;&lt;/td&gt;&lt;/tr&gt;
  832. &lt;tr&gt;&lt;td&gt;&lt;b&gt;
  833. infeedLoadStatus&lt;/b&gt;&lt;/td&gt;&lt;td&gt;
  834. %parm[#4]%;&lt;/td&gt;&lt;td&gt;&lt;p&gt;
  835. normal(0)
  836. notOn(1)
  837. reading(2)
  838. loadLow(3)
  839. loadHigh(4)
  840. overLoad(5)
  841. readError(6)
  842. noComm(7)
  843. &lt;/p&gt;&lt;/td&gt;&lt;/tr&gt;
  844. &lt;tr&gt;&lt;td&gt;&lt;b&gt;
  845. infeedLoadValue&lt;/b&gt;&lt;/td&gt;&lt;td&gt;
  846. %parm[#5]%;&lt;/td&gt;&lt;td&gt;&lt;p&gt;&lt;/p&gt;&lt;/td&gt;&lt;/tr&gt;
  847. &lt;tr&gt;&lt;td&gt;&lt;b&gt;
  848. infeedLoadHighThresh&lt;/b&gt;&lt;/td&gt;&lt;td&gt;
  849. %parm[#6]%;&lt;/td&gt;&lt;td&gt;&lt;p&gt;&lt;/p&gt;&lt;/td&gt;&lt;/tr&gt;&lt;/table&gt;
  850. </descr>
  851. <logmsg dest='logndisplay'>&lt;p&gt;
  852. Sentry Event: infeedLoadEvent normal trap received
  853. systemLocation=%parm[#1]%
  854. infeedID=%parm[#2]%
  855. infeedName=%parm[#3]%
  856. infeedLoadStatus=%parm[#4]%
  857. infeedLoadValue=%parm[#5]%
  858. infeedLoadHighThresh=%parm[#6]%&lt;/p&gt;
  859. </logmsg>
  860. <severity>Normal</severity>
  861. <alarm-data reduction-key="%uei%:%dpname%:%nodeid%:%interface%:%parm[#2]%:%parm[#3]%" alarm-type="2" clear-key="uei.opennms.org/vendor/ServerTech/traps/infeedLoadEvent-Error:%dpname%:%nodeid%:%interface%:%parm[#2]%i:%parm[#3]%" auto-clean="false"/>
  862. </event>
  863. <event>
  864. <mask>
  865. <maskelement>
  866. <mename>id</mename>
  867. <mevalue>.1.3.6.1.4.1.1718.3.100</mevalue>
  868. </maskelement>
  869. <maskelement>
  870. <mename>generic</mename>
  871. <mevalue>6</mevalue>
  872. </maskelement>
  873. <maskelement>
  874. <mename>specific</mename>
  875. <mevalue>3</mevalue>
  876. </maskelement>
  877. <varbind>
  878. <vbnumber>4</vbnumber>
  879. <vbvalue>1</vbvalue>
  880. </varbind>
  881. </mask>
  882. <uei>uei.opennms.org/vendor/ServerTech/traps/infeedLoadEvent-Normal</uei>
  883. <event-label>Sentry3-MIB defined trap event: infeedLoadEvent-Normal</event-label>
  884. <descr>
  885. &lt;p&gt;Input feed load event. If enabled, this trap is sent when
  886. the infeedLoadStatus indicates an error state ('loadLow',
  887. 'loadHigh', 'overLoad', 'readError', or 'noComm'). This
  888. trap is repeated periodically while the infeedLoadStatus
  889. remains in an error state. If the infeedLoadStatus returns
  890. to a non-error state ('normal' or 'notOn'), this trap is
  891. sent once more with the non-error infeedLoadStatus, and then
  892. stops being repeated.&lt;/p&gt;&lt;table&gt;
  893. &lt;tr&gt;&lt;td&gt;&lt;b&gt;
  894. systemLocation&lt;/b&gt;&lt;/td&gt;&lt;td&gt;
  895. %parm[#1]%;&lt;/td&gt;&lt;td&gt;&lt;p&gt;&lt;/p&gt;&lt;/td&gt;&lt;/tr&gt;
  896. &lt;tr&gt;&lt;td&gt;&lt;b&gt;
  897. infeedID&lt;/b&gt;&lt;/td&gt;&lt;td&gt;
  898. %parm[#2]%;&lt;/td&gt;&lt;td&gt;&lt;p&gt;&lt;/p&gt;&lt;/td&gt;&lt;/tr&gt;
  899. &lt;tr&gt;&lt;td&gt;&lt;b&gt;
  900. infeedName&lt;/b&gt;&lt;/td&gt;&lt;td&gt;
  901. %parm[#3]%;&lt;/td&gt;&lt;td&gt;&lt;p&gt;&lt;/p&gt;&lt;/td&gt;&lt;/tr&gt;
  902. &lt;tr&gt;&lt;td&gt;&lt;b&gt;
  903. infeedLoadStatus&lt;/b&gt;&lt;/td&gt;&lt;td&gt;
  904. %parm[#4]%;&lt;/td&gt;&lt;td&gt;&lt;p&gt;
  905. normal(0)
  906. notOn(1)
  907. reading(2)
  908. loadLow(3)
  909. loadHigh(4)
  910. overLoad(5)
  911. readError(6)
  912. noComm(7)
  913. &lt;/p&gt;&lt;/td&gt;&lt;/tr&gt;
  914. &lt;tr&gt;&lt;td&gt;&lt;b&gt;
  915. infeedLoadValue&lt;/b&gt;&lt;/td&gt;&lt;td&gt;
  916. %parm[#5]%;&lt;/td&gt;&lt;td&gt;&lt;p&gt;&lt;/p&gt;&lt;/td&gt;&lt;/tr&gt;
  917. &lt;tr&gt;&lt;td&gt;&lt;b&gt;
  918. infeedLoadHighThresh&lt;/b&gt;&lt;/td&gt;&lt;td&gt;
  919. %parm[#6]%;&lt;/td&gt;&lt;td&gt;&lt;p&gt;&lt;/p&gt;&lt;/td&gt;&lt;/tr&gt;&lt;/table&gt;
  920. </descr>
  921. <logmsg dest='logndisplay'>&lt;p&gt;
  922. Sentry Event: infeedLoadEvent notOn trap received
  923. systemLocation=%parm[#1]%
  924. infeedID=%parm[#2]%
  925. infeedName=%parm[#3]%
  926. infeedLoadStatus=%parm[#4]%
  927. infeedLoadValue=%parm[#5]%
  928. infeedLoadHighThresh=%parm[#6]%&lt;/p&gt;
  929. </logmsg>
  930. <severity>Normal</severity>
  931. <alarm-data reduction-key="%uei%:%dpname%:%nodeid%:%interface%:%parm[#2]%:%parm[#3]%" alarm-type="2" clear-key="uei.opennms.org/vendor/ServerTech/traps/infeedLoadEvent-Error:%dpname%:%nodeid%:%interface%:%parm[#2]%i:%parm[#3]%" auto-clean="false"/>
  932. </event>
  933. <event>
  934. <mask>
  935. <maskelement>
  936. <mename>id</mename>
  937. <mevalue>.1.3.6.1.4.1.1718.3.100</mevalue>
  938. </maskelement>
  939. <maskelement>
  940. <mename>generic</mename>
  941. <mevalue>6</mevalue>
  942. </maskelement>
  943. <maskelement>
  944. <mename>specific</mename>
  945. <mevalue>3</mevalue>
  946. </maskelement>
  947. <varbind>
  948. <vbnumber>4</vbnumber>
  949. <vbvalue>2</vbvalue>
  950. </varbind>
  951. </mask>
  952. <uei>uei.opennms.org/vendor/ServerTech/traps/infeedLoadEvent-Error</uei>
  953. <event-label>Sentry3-MIB defined trap event: infeedLoadEvent-Error</event-label>
  954. <descr>
  955. &lt;p&gt;Input feed load event. If enabled, this trap is sent when
  956. the infeedLoadStatus indicates an error state ('loadLow',
  957. 'loadHigh', 'overLoad', 'readError', or 'noComm'). This
  958. trap is repeated periodically while the infeedLoadStatus
  959. remains in an error state. If the infeedLoadStatus returns
  960. to a non-error state ('normal' or 'notOn'), this trap is
  961. sent once more with the non-error infeedLoadStatus, and then
  962. stops being repeated.&lt;/p&gt;&lt;table&gt;
  963. &lt;tr&gt;&lt;td&gt;&lt;b&gt;
  964. systemLocation&lt;/b&gt;&lt;/td&gt;&lt;td&gt;
  965. %parm[#1]%;&lt;/td&gt;&lt;td&gt;&lt;p&gt;&lt;/p&gt;&lt;/td&gt;&lt;/tr&gt;
  966. &lt;tr&gt;&lt;td&gt;&lt;b&gt;
  967. infeedID&lt;/b&gt;&lt;/td&gt;&lt;td&gt;
  968. %parm[#2]%;&lt;/td&gt;&lt;td&gt;&lt;p&gt;&lt;/p&gt;&lt;/td&gt;&lt;/tr&gt;
  969. &lt;tr&gt;&lt;td&gt;&lt;b&gt;
  970. infeedName&lt;/b&gt;&lt;/td&gt;&lt;td&gt;
  971. %parm[#3]%;&lt;/td&gt;&lt;td&gt;&lt;p&gt;&lt;/p&gt;&lt;/td&gt;&lt;/tr&gt;
  972. &lt;tr&gt;&lt;td&gt;&lt;b&gt;
  973. infeedLoadStatus&lt;/b&gt;&lt;/td&gt;&lt;td&gt;
  974. %parm[#4]%;&lt;/td&gt;&lt;td&gt;&lt;p&gt;
  975. normal(0)
  976. notOn(1)
  977. reading(2)
  978. loadLow(3)
  979. loadHigh(4)
  980. overLoad(5)
  981. readError(6)
  982. noComm(7)
  983. &lt;/p&gt;&lt;/td&gt;&lt;/tr&gt;
  984. &lt;tr&gt;&lt;td&gt;&lt;b&gt;
  985. infeedLoadValue&lt;/b&gt;&lt;/td&gt;&lt;td&gt;
  986. %parm[#5]%;&lt;/td&gt;&lt;td&gt;&lt;p&gt;&lt;/p&gt;&lt;/td&gt;&lt;/tr&gt;
  987. &lt;tr&gt;&lt;td&gt;&lt;b&gt;
  988. infeedLoadHighThresh&lt;/b&gt;&lt;/td&gt;&lt;td&gt;
  989. %parm[#6]%;&lt;/td&gt;&lt;td&gt;&lt;p&gt;&lt;/p&gt;&lt;/td&gt;&lt;/tr&gt;&lt;/table&gt;
  990. </descr>
  991. <logmsg dest='logndisplay'>&lt;p&gt;
  992. Sentry Event: infeedLoadEvent reading trap received
  993. systemLocation=%parm[#1]%
  994. infeedID=%parm[#2]%
  995. infeedName=%parm[#3]%
  996. infeedLoadStatus=%parm[#4]%
  997. infeedLoadValue=%parm[#5]%
  998. infeedLoadHighThresh=%parm[#6]%&lt;/p&gt;
  999. </logmsg>
  1000. <severity>Warning</severity>
  1001. <alarm-data reduction-key="%uei%:%dpname%:%nodeid%:%interface%:%parm[#2]%:%parm[#3]%" alarm-type="1" auto-clean="false"/>
  1002. </event>
  1003. <event>
  1004. <mask>
  1005. <maskelement>
  1006. <mename>id</mename>
  1007. <mevalue>.1.3.6.1.4.1.1718.3.100</mevalue>
  1008. </maskelement>
  1009. <maskelement>
  1010. <mename>generic</mename>
  1011. <mevalue>6</mevalue>
  1012. </maskelement>
  1013. <maskelement>
  1014. <mename>specific</mename>
  1015. <mevalue>3</mevalue>
  1016. </maskelement>
  1017. <varbind>
  1018. <vbnumber>4</vbnumber>
  1019. <vbvalue>3</vbvalue>
  1020. </varbind>
  1021. </mask>
  1022. <uei>uei.opennms.org/vendor/ServerTech/traps/infeedLoadEvent-Error</uei>
  1023. <event-label>Sentry3-MIB defined trap event: infeedLoadEvent-Error</event-label>
  1024. <descr>
  1025. &lt;p&gt;Input feed load event. If enabled, this trap is sent when
  1026. the infeedLoadStatus indicates an error state ('loadLow',
  1027. 'loadHigh', 'overLoad', 'readError', or 'noComm'). This
  1028. trap is repeated periodically while the infeedLoadStatus
  1029. remains in an error state. If the infeedLoadStatus returns
  1030. to a non-error state ('normal' or 'notOn'), this trap is
  1031. sent once more with the non-error infeedLoadStatus, and then
  1032. stops being repeated.&lt;/p&gt;&lt;table&gt;
  1033. &lt;tr&gt;&lt;td&gt;&lt;b&gt;
  1034. systemLocation&lt;/b&gt;&lt;/td&gt;&lt;td&gt;
  1035. %parm[#1]%;&lt;/td&gt;&lt;td&gt;&lt;p&gt;&lt;/p&gt;&lt;/td&gt;&lt;/tr&gt;
  1036. &lt;tr&gt;&lt;td&gt;&lt;b&gt;
  1037. infeedID&lt;/b&gt;&lt;/td&gt;&lt;td&gt;
  1038. %parm[#2]%;&lt;/td&gt;&lt;td&gt;&lt;p&gt;&lt;/p&gt;&lt;/td&gt;&lt;/tr&gt;
  1039. &lt;tr&gt;&lt;td&gt;&lt;b&gt;
  1040. infeedName&lt;/b&gt;&lt;/td&gt;&lt;td&gt;
  1041. %parm[#3]%;&lt;/td&gt;&lt;td&gt;&lt;p&gt;&lt;/p&gt;&lt;/td&gt;&lt;/tr&gt;
  1042. &lt;tr&gt;&lt;td&gt;&lt;b&gt;
  1043. infeedLoadStatus&lt;/b&gt;&lt;/td&gt;&lt;td&gt;
  1044. %parm[#4]%;&lt;/td&gt;&lt;td&gt;&lt;p&gt;
  1045. normal(0)
  1046. notOn(1)
  1047. reading(2)
  1048. loadLow(3)
  1049. loadHigh(4)
  1050. overLoad(5)
  1051. readError(6)
  1052. noComm(7)
  1053. &lt;/p&gt;&lt;/td&gt;&lt;/tr&gt;
  1054. &lt;tr&gt;&lt;td&gt;&lt;b&gt;
  1055. infeedLoadValue&lt;/b&gt;&lt;/td&gt;&lt;td&gt;
  1056. %parm[#5]%;&lt;/td&gt;&lt;td&gt;&lt;p&gt;&lt;/p&gt;&lt;/td&gt;&lt;/tr&gt;
  1057. &lt;tr&gt;&lt;td&gt;&lt;b&gt;
  1058. infeedLoadHighThresh&lt;/b&gt;&lt;/td&gt;&lt;td&gt;
  1059. %parm[#6]%;&lt;/td&gt;&lt;td&gt;&lt;p&gt;&lt;/p&gt;&lt;/td&gt;&lt;/tr&gt;&lt;/table&gt;
  1060. </descr>
  1061. <logmsg dest='logndisplay'>&lt;p&gt;
  1062. Sentry Event: infeedLoadEvent low load trap received
  1063. systemLocation=%parm[#1]%
  1064. infeedID=%parm[#2]%
  1065. infeedName=%parm[#3]%
  1066. infeedLoadStatus=%parm[#4]%
  1067. infeedLoadValue=%parm[#5]%
  1068. infeedLoadHighThresh=%parm[#6]%&lt;/p&gt;
  1069. </logmsg>
  1070. <severity>Minor</severity>
  1071. <alarm-data reduction-key="%uei%:%dpname%:%nodeid%:%interface%:%parm[#2]%:%parm[#3]%" alarm-type="1" auto-clean="false"/>
  1072. </event>
  1073. <event>
  1074. <mask>
  1075. <maskelement>
  1076. <mename>id</mename>
  1077. <mevalue>.1.3.6.1.4.1.1718.3.100</mevalue>
  1078. </maskelement>
  1079. <maskelement>
  1080. <mename>generic</mename>
  1081. <mevalue>6</mevalue>
  1082. </maskelement>
  1083. <maskelement>
  1084. <mename>specific</mename>
  1085. <mevalue>3</mevalue>
  1086. </maskelement>
  1087. <varbind>
  1088. <vbnumber>4</vbnumber>
  1089. <vbvalue>4</vbvalue>
  1090. </varbind>
  1091. </mask>
  1092. <uei>uei.opennms.org/vendor/ServerTech/traps/infeedLoadEvent-Error</uei>
  1093. <event-label>Sentry3-MIB defined trap event: infeedLoadEvent-Error</event-label>
  1094. <descr>
  1095. &lt;p&gt;Input feed load event. If enabled, this trap is sent when
  1096. the infeedLoadStatus indicates an error state ('loadLow',
  1097. 'loadHigh', 'overLoad', 'readError', or 'noComm'). This
  1098. trap is repeated periodically while the infeedLoadStatus
  1099. remains in an error state. If the infeedLoadStatus returns
  1100. to a non-error state ('normal' or 'notOn'), this trap is
  1101. sent once more with the non-error infeedLoadStatus, and then
  1102. stops being repeated.&lt;/p&gt;&lt;table&gt;
  1103. &lt;tr&gt;&lt;td&gt;&lt;b&gt;
  1104. systemLocation&lt;/b&gt;&lt;/td&gt;&lt;td&gt;
  1105. %parm[#1]%;&lt;/td&gt;&lt;td&gt;&lt;p&gt;&lt;/p&gt;&lt;/td&gt;&lt;/tr&gt;
  1106. &lt;tr&gt;&lt;td&gt;&lt;b&gt;
  1107. infeedID&lt;/b&gt;&lt;/td&gt;&lt;td&gt;
  1108. %parm[#2]%;&lt;/td&gt;&lt;td&gt;&lt;p&gt;&lt;/p&gt;&lt;/td&gt;&lt;/tr&gt;
  1109. &lt;tr&gt;&lt;td&gt;&lt;b&gt;
  1110. infeedName&lt;/b&gt;&lt;/td&gt;&lt;td&gt;
  1111. %parm[#3]%;&lt;/td&gt;&lt;td&gt;&lt;p&gt;&lt;/p&gt;&lt;/td&gt;&lt;/tr&gt;
  1112. &lt;tr&gt;&lt;td&gt;&lt;b&gt;
  1113. infeedLoadStatus&lt;/b&gt;&lt;/td&gt;&lt;td&gt;
  1114. %parm[#4]%;&lt;/td&gt;&lt;td&gt;&lt;p&gt;
  1115. normal(0)
  1116. notOn(1)
  1117. reading(2)
  1118. loadLow(3)
  1119. loadHigh(4)
  1120. overLoad(5)
  1121. readError(6)
  1122. noComm(7)
  1123. &lt;/p&gt;&lt;/td&gt;&lt;/tr&gt;
  1124. &lt;tr&gt;&lt;td&gt;&lt;b&gt;
  1125. infeedLoadValue&lt;/b&gt;&lt;/td&gt;&lt;td&gt;
  1126. %parm[#5]%;&lt;/td&gt;&lt;td&gt;&lt;p&gt;&lt;/p&gt;&lt;/td&gt;&lt;/tr&gt;
  1127. &lt;tr&gt;&lt;td&gt;&lt;b&gt;
  1128. infeedLoadHighThresh&lt;/b&gt;&lt;/td&gt;&lt;td&gt;
  1129. %parm[#6]%;&lt;/td&gt;&lt;td&gt;&lt;p&gt;&lt;/p&gt;&lt;/td&gt;&lt;/tr&gt;&lt;/table&gt;
  1130. </descr>
  1131. <logmsg dest='logndisplay'>&lt;p&gt;
  1132. Sentry Event: infeedLoadEvent high load trap received
  1133. systemLocation=%parm[#1]%
  1134. infeedID=%parm[#2]%
  1135. infeedName=%parm[#3]%
  1136. infeedLoadStatus=%parm[#4]%
  1137. infeedLoadValue=%parm[#5]%
  1138. infeedLoadHighThresh=%parm[#6]%&lt;/p&gt;
  1139. </logmsg>
  1140. <severity>Minor</severity>
  1141. <alarm-data reduction-key="%uei%:%dpname%:%nodeid%:%interface%:%parm[#2]%:%parm[#3]%" alarm-type="1" auto-clean="false"/>
  1142. </event>
  1143. <event>
  1144. <mask>
  1145. <maskelement>
  1146. <mename>id</mename>
  1147. <mevalue>.1.3.6.1.4.1.1718.3.100</mevalue>
  1148. </maskelement>
  1149. <maskelement>
  1150. <mename>generic</mename>
  1151. <mevalue>6</mevalue>
  1152. </maskelement>
  1153. <maskelement>
  1154. <mename>specific</mename>
  1155. <mevalue>3</mevalue>
  1156. </maskelement>
  1157. <varbind>
  1158. <vbnumber>4</vbnumber>
  1159. <vbvalue>5</vbvalue>
  1160. </varbind>
  1161. </mask>
  1162. <uei>uei.opennms.org/vendor/ServerTech/traps/infeedLoadEvent-Error</uei>
  1163. <event-label>Sentry3-MIB defined trap event: infeedLoadEvent-Error</event-label>
  1164. <descr>
  1165. &lt;p&gt;Input feed load event. If enabled, this trap is sent when
  1166. the infeedLoadStatus indicates an error state ('loadLow',
  1167. 'loadHigh', 'overLoad', 'readError', or 'noComm'). This
  1168. trap is repeated periodically while the infeedLoadStatus
  1169. remains in an error state. If the infeedLoadStatus returns
  1170. to a non-error state ('normal' or 'notOn'), this trap is
  1171. sent once more with the non-error infeedLoadStatus, and then
  1172. stops being repeated.&lt;/p&gt;&lt;table&gt;
  1173. &lt;tr&gt;&lt;td&gt;&lt;b&gt;
  1174. systemLocation&lt;/b&gt;&lt;/td&gt;&lt;td&gt;
  1175. %parm[#1]%;&lt;/td&gt;&lt;td&gt;&lt;p&gt;&lt;/p&gt;&lt;/td&gt;&lt;/tr&gt;
  1176. &lt;tr&gt;&lt;td&gt;&lt;b&gt;
  1177. infeedID&lt;/b&gt;&lt;/td&gt;&lt;td&gt;
  1178. %parm[#2]%;&lt;/td&gt;&lt;td&gt;&lt;p&gt;&lt;/p&gt;&lt;/td&gt;&lt;/tr&gt;
  1179. &lt;tr&gt;&lt;td&gt;&lt;b&gt;
  1180. infeedName&lt;/b&gt;&lt;/td&gt;&lt;td&gt;
  1181. %parm[#3]%;&lt;/td&gt;&lt;td&gt;&lt;p&gt;&lt;/p&gt;&lt;/td&gt;&lt;/tr&gt;
  1182. &lt;tr&gt;&lt;td&gt;&lt;b&gt;
  1183. infeedLoadStatus&lt;/b&gt;&lt;/td&gt;&lt;td&gt;
  1184. %parm[#4]%;&lt;/td&gt;&lt;td&gt;&lt;p&gt;
  1185. normal(0)
  1186. notOn(1)
  1187. reading(2)
  1188. loadLow(3)
  1189. loadHigh(4)
  1190. overLoad(5)
  1191. readError(6)
  1192. noComm(7)
  1193. &lt;/p&gt;&lt;/td&gt;&lt;/tr&gt;
  1194. &lt;tr&gt;&lt;td&gt;&lt;b&gt;
  1195. infeedLoadValue&lt;/b&gt;&lt;/td&gt;&lt;td&gt;
  1196. %parm[#5]%;&lt;/td&gt;&lt;td&gt;&lt;p&gt;&lt;/p&gt;&lt;/td&gt;&lt;/tr&gt;
  1197. &lt;tr&gt;&lt;td&gt;&lt;b&gt;
  1198. infeedLoadHighThresh&lt;/b&gt;&lt;/td&gt;&lt;td&gt;
  1199. %parm[#6]%;&lt;/td&gt;&lt;td&gt;&lt;p&gt;&lt;/p&gt;&lt;/td&gt;&lt;/tr&gt;&lt;/table&gt;
  1200. </descr>
  1201. <logmsg dest='logndisplay'>&lt;p&gt;
  1202. Sentry Event: infeedLoadEvent over load trap received
  1203. systemLocation=%parm[#1]%
  1204. infeedID=%parm[#2]%
  1205. infeedName=%parm[#3]%
  1206. infeedLoadStatus=%parm[#4]%
  1207. infeedLoadValue=%parm[#5]%
  1208. infeedLoadHighThresh=%parm[#6]%&lt;/p&gt;
  1209. </logmsg>
  1210. <severity>Minor</severity>
  1211. <alarm-data reduction-key="%uei%:%dpname%:%nodeid%:%interface%:%parm[#2]%:%parm[#3]%" alarm-type="1" auto-clean="false"/>
  1212. </event>
  1213. <event>
  1214. <mask>
  1215. <maskelement>
  1216. <mename>id</mename>
  1217. <mevalue>.1.3.6.1.4.1.1718.3.100</mevalue>
  1218. </maskelement>
  1219. <maskelement>
  1220. <mename>generic</mename>
  1221. <mevalue>6</mevalue>
  1222. </maskelement>
  1223. <maskelement>
  1224. <mename>specific</mename>
  1225. <mevalue>3</mevalue>
  1226. </maskelement>
  1227. <varbind>
  1228. <vbnumber>4</vbnumber>
  1229. <vbvalue>6</vbvalue>
  1230. </varbind>
  1231. </mask>
  1232. <uei>uei.opennms.org/vendor/ServerTech/traps/infeedLoadEvent-Error</uei>
  1233. <event-label>Sentry3-MIB defined trap event: infeedLoadEvent-Error</event-label>
  1234. <descr>
  1235. &lt;p&gt;Input feed load event. If enabled, this trap is sent when
  1236. the infeedLoadStatus indicates an error state ('loadLow',
  1237. 'loadHigh', 'overLoad', 'readError', or 'noComm'). This
  1238. trap is repeated periodically while the infeedLoadStatus
  1239. remains in an error state. If the infeedLoadStatus returns
  1240. to a non-error state ('normal' or 'notOn'), this trap is
  1241. sent once more with the non-error infeedLoadStatus, and then
  1242. stops being repeated.&lt;/p&gt;&lt;table&gt;
  1243. &lt;tr&gt;&lt;td&gt;&lt;b&gt;
  1244. systemLocation&lt;/b&gt;&lt;/td&gt;&lt;td&gt;
  1245. %parm[#1]%;&lt;/td&gt;&lt;td&gt;&lt;p&gt;&lt;/p&gt;&lt;/td&gt;&lt;/tr&gt;
  1246. &lt;tr&gt;&lt;td&gt;&lt;b&gt;
  1247. infeedID&lt;/b&gt;&lt;/td&gt;&lt;td&gt;
  1248. %parm[#2]%;&lt;/td&gt;&lt;td&gt;&lt;p&gt;&lt;/p&gt;&lt;/td&gt;&lt;/tr&gt;
  1249. &lt;tr&gt;&lt;td&gt;&lt;b&gt;
  1250. infeedName&lt;/b&gt;&lt;/td&gt;&lt;td&gt;
  1251. %parm[#3]%;&lt;/td&gt;&lt;td&gt;&lt;p&gt;&lt;/p&gt;&lt;/td&gt;&lt;/tr&gt;
  1252. &lt;tr&gt;&lt;td&gt;&lt;b&gt;
  1253. infeedLoadStatus&lt;/b&gt;&lt;/td&gt;&lt;td&gt;
  1254. %parm[#4]%;&lt;/td&gt;&lt;td&gt;&lt;p&gt;
  1255. normal(0)
  1256. notOn(1)
  1257. reading(2)
  1258. loadLow(3)
  1259. loadHigh(4)
  1260. overLoad(5)
  1261. readError(6)
  1262. noComm(7)
  1263. &lt;/p&gt;&lt;/td&gt;&lt;/tr&gt;
  1264. &lt;tr&gt;&lt;td&gt;&lt;b&gt;
  1265. infeedLoadValue&lt;/b&gt;&lt;/td&gt;&lt;td&gt;
  1266. %parm[#5]%;&lt;/td&gt;&lt;td&gt;&lt;p&gt;&lt;/p&gt;&lt;/td&gt;&lt;/tr&gt;
  1267. &lt;tr&gt;&lt;td&gt;&lt;b&gt;
  1268. infeedLoadHighThresh&lt;/b&gt;&lt;/td&gt;&lt;td&gt;
  1269. %parm[#6]%;&lt;/td&gt;&lt;td&gt;&lt;p&gt;&lt;/p&gt;&lt;/td&gt;&lt;/tr&gt;&lt;/table&gt;
  1270. </descr>
  1271. <logmsg dest='logndisplay'>&lt;p&gt;
  1272. Sentry Event: infeedLoadEvent read error trap received
  1273. systemLocation=%parm[#1]%
  1274. infeedID=%parm[#2]%
  1275. infeedName=%parm[#3]%
  1276. infeedLoadStatus=%parm[#4]%
  1277. infeedLoadValue=%parm[#5]%
  1278. infeedLoadHighThresh=%parm[#6]%&lt;/p&gt;
  1279. </logmsg>
  1280. <severity>Minor</severity>
  1281. <alarm-data reduction-key="%uei%:%dpname%:%nodeid%:%interface%:%parm[#2]%:%parm[#3]%" alarm-type="1" auto-clean="false"/>
  1282. </event>
  1283. <event>
  1284. <mask>
  1285. <maskelement>
  1286. <mename>id</mename>
  1287. <mevalue>.1.3.6.1.4.1.1718.3.100</mevalue>
  1288. </maskelement>
  1289. <maskelement>
  1290. <mename>generic</mename>
  1291. <mevalue>6</mevalue>
  1292. </maskelement>
  1293. <maskelement>
  1294. <mename>specific</mename>
  1295. <mevalue>3</mevalue>
  1296. </maskelement>
  1297. <varbind>
  1298. <vbnumber>4</vbnumber>
  1299. <vbvalue>7</vbvalue>
  1300. </varbind>
  1301. </mask>
  1302. <uei>uei.opennms.org/vendor/ServerTech/traps/infeedLoadEvent-Error</uei>
  1303. <event-label>Sentry3-MIB defined trap event: infeedLoadEvent-Error</event-label>
  1304. <descr>
  1305. &lt;p&gt;Input feed load event. If enabled, this trap is sent when
  1306. the infeedLoadStatus indicates an error state ('loadLow',
  1307. 'loadHigh', 'overLoad', 'readError', or 'noComm'). This
  1308. trap is repeated periodically while the infeedLoadStatus
  1309. remains in an error state. If the infeedLoadStatus returns
  1310. to a non-error state ('normal' or 'notOn'), this trap is
  1311. sent once more with the non-error infeedLoadStatus, and then
  1312. stops being repeated.&lt;/p&gt;&lt;table&gt;
  1313. &lt;tr&gt;&lt;td&gt;&lt;b&gt;
  1314. systemLocation&lt;/b&gt;&lt;/td&gt;&lt;td&gt;
  1315. %parm[#1]%;&lt;/td&gt;&lt;td&gt;&lt;p&gt;&lt;/p&gt;&lt;/td&gt;&lt;/tr&gt;
  1316. &lt;tr&gt;&lt;td&gt;&lt;b&gt;
  1317. infeedID&lt;/b&gt;&lt;/td&gt;&lt;td&gt;
  1318. %parm[#2]%;&lt;/td&gt;&lt;td&gt;&lt;p&gt;&lt;/p&gt;&lt;/td&gt;&lt;/tr&gt;
  1319. &lt;tr&gt;&lt;td&gt;&lt;b&gt;
  1320. infeedName&lt;/b&gt;&lt;/td&gt;&lt;td&gt;
  1321. %parm[#3]%;&lt;/td&gt;&lt;td&gt;&lt;p&gt;&lt;/p&gt;&lt;/td&gt;&lt;/tr&gt;
  1322. &lt;tr&gt;&lt;td&gt;&lt;b&gt;
  1323. infeedLoadStatus&lt;/b&gt;&lt;/td&gt;&lt;td&gt;
  1324. %parm[#4]%;&lt;/td&gt;&lt;td&gt;&lt;p&gt;
  1325. normal(0)
  1326. notOn(1)
  1327. reading(2)
  1328. loadLow(3)
  1329. loadHigh(4)
  1330. overLoad(5)
  1331. readError(6)
  1332. noComm(7)
  1333. &lt;/p&gt;&lt;/td&gt;&lt;/tr&gt;
  1334. &lt;tr&gt;&lt;td&gt;&lt;b&gt;
  1335. infeedLoadValue&lt;/b&gt;&lt;/td&gt;&lt;td&gt;
  1336. %parm[#5]%;&lt;/td&gt;&lt;td&gt;&lt;p&gt;&lt;/p&gt;&lt;/td&gt;&lt;/tr&gt;
  1337. &lt;tr&gt;&lt;td&gt;&lt;b&gt;
  1338. infeedLoadHighThresh&lt;/b&gt;&lt;/td&gt;&lt;td&gt;
  1339. %parm[#6]%;&lt;/td&gt;&lt;td&gt;&lt;p&gt;&lt;/p&gt;&lt;/td&gt;&lt;/tr&gt;&lt;/table&gt;
  1340. </descr>
  1341. <logmsg dest='logndisplay'>&lt;p&gt;
  1342. Sentry Event: infeedLoadEvent noComm trap received
  1343. systemLocation=%parm[#1]%
  1344. infeedID=%parm[#2]%
  1345. infeedName=%parm[#3]%
  1346. infeedLoadStatus=%parm[#4]%
  1347. infeedLoadValue=%parm[#5]%
  1348. infeedLoadHighThresh=%parm[#6]%&lt;/p&gt;
  1349. </logmsg>
  1350. <severity>Minor</severity>
  1351. <alarm-data reduction-key="%uei%:%dpname%:%nodeid%:%interface%:%parm[#2]%:%parm[#3]%" alarm-type="1" auto-clean="false"/>
  1352. </event>
  1353. <event>
  1354. <mask>
  1355. <maskelement>
  1356. <mename>id</mename>
  1357. <mevalue>.1.3.6.1.4.1.1718.3.100</mevalue>
  1358. </maskelement>
  1359. <maskelement>
  1360. <mename>generic</mename>
  1361. <mevalue>6</mevalue>
  1362. </maskelement>
  1363. <maskelement>
  1364. <mename>specific</mename>
  1365. <mevalue>3</mevalue>
  1366. </maskelement>
  1367. </mask>
  1368. <uei>uei.opennms.org/vendor/ServerTech/traps/infeedLoadEvent</uei>
  1369. <event-label>Sentry3-MIB defined trap event: infeedLoadEvent</event-label>
  1370. <descr>
  1371. &lt;p&gt;Input feed load event. If enabled, this trap is sent when
  1372. the infeedLoadStatus indicates an error state ('loadLow',
  1373. 'loadHigh', 'overLoad', 'readError', or 'noComm'). This
  1374. trap is repeated periodically while the infeedLoadStatus
  1375. remains in an error state. If the infeedLoadStatus returns
  1376. to a non-error state ('normal' or 'notOn'), this trap is
  1377. sent once more with the non-error infeedLoadStatus, and then
  1378. stops being repeated.&lt;/p&gt;&lt;table&gt;
  1379. &lt;tr&gt;&lt;td&gt;&lt;b&gt;
  1380. systemLocation&l